Sprinkler System Maintenance & Winterization: How to Safeguard Building Sprinkler Systems against Freezing Failures
October 17, 2026
October 17, 2026
It’s that time of year again – the leaves are changing colour, the days are getting shorter, and that familiar chill is in the air. The transition from summer to fall signals that it’s time for a host of modified routines and behaviours as we prepare for the colder months ahead. For the owners and managers of buildings containing sprinkler systems, it’s time for maintenance and winterization of those systems. While these tasks may feel like a simple box to be checked every fall, when it comes to life-saving systems, it’s critical to ensure they are functional in case of an emergency.
A building’s sprinkler system is a complex, integrated system of pipes, fittings, valves, sprinkler heads, pumps, sensors, alarms, and other components, which are often located in concealed parts of buildings, such as behind drywall or in crawl spaces. These systems contain water pressure that can often exceed domestic water pressure. As a result, a leak from a failed component can release a significant amount of water in a short period of time, causing property damage that often exceeds the building’s water damage deductible. Regular maintenance and winterization of sprinkler systems are critical as they can help to prevent these leak events.
Every year, 30 Forensic Engineering’s Materials & Product Failure group investigates a significant number of water losses caused by the freezing of sprinkler systems. In each case, we help insurers, legal teams, and property owners and managers understand the root cause of the failure, which often includes an assessment of the design and installation, as well as the inspection, testing, and maintenance (“ITM”) of the sprinkler system. In many cases, we have found that a better understanding of the system’s fundamentals could have prevented the freezing failure from occurring.
In this article, we will describe our investigation process with respect to freezing failures in sprinkler systems. These investigations typically comprise two phases:
For simplicity, the examples in this series will be limited to ruptured sprinkler pipes, but investigations into other failures (e.g., fittings, valves, and sprinkler heads) would involve a similar investigation.
Fractography is a method in failure analysis that all materials engineers learn as part of their education. The first step in fractography is to employ different techniques, such as visual examination, microscopic examination, and/or chemical characterization, to examine a fractured component and determine how that fracture occurred. The characteristic features of a fracture not only depend on how the fracture occurred (the “fracture mechanism”), but also what the component is made of (the “component material”).

As an example, we would evaluate the macroscopic features of a failed sprinkler pipe, as they could differentiate a freezing fracture from other fracture mechanisms. These features will differ depending on the pipe material and conditions experienced by the pipe.
Black steel pipes are often used in modern sprinkler systems, while many older systems used cast iron pipes. Along a length of steel pipe, freezing will usually result in a ductile fracture, which is characterized as a wide crack in the centre of a bulged pipe wall (Figure 1 A). Material deformation absorbs some of the excess pressure before the component cracks. As soon as the crack opens, the excess water pressure is immediately relieved. As such, we usually only see one crack in a pipe section. This differs from other fracture mechanisms, such as corrosion (Figure 1 B), where we would expect to see discolouration (rust) and material loss from the pipe wall, weakening the pipe in specific locations. This could result in pinhole leaks or multiple cracks along a pipe length.
Chlorinated polyvinyl chloride (“CPVC,” a thermoplastic) is a plastic material used in sprinkler pipes. CPVC is more brittle than cast iron and steel, and, consequently, an overpressurization failure will result in a more brittle fracture appearance. With less deformation, or bulging, available to absorb some of the force, enough energy is produced for the crack to propagate in multiple directions (known as “crack branches”) (Figure 2 A). The directions of the branches are normally continuous, making them easy to trace back to a common origin.

In a case where cracking occurs due to material degradation from an environmental factor, multiple, very tight cracks can form due to local loss of material properties (Figure 2 B). These cracks would be even tighter than overpressurization cracks and may not be continuous if the material was degraded in multiple locations.
In summary, fractography is a method used to evaluate how a failure occurred. Macroscopic and microscopic features, as well as chemical analysis and other techniques, are used at this stage. Freezing failures will usually have the appearance of an overpressurization failure, which has features which differ from corrosion or material degradation. However, fractography on its own would not tell the whole story of why freezing occurred in the first place.
Once we’ve established that a sprinkler pipe likely failed due to freezing, we must look at the sprinkler system to determine why it was in a position to freeze.
The two common types of sprinkler systems found in residential and commercial buildings are wet pipe systems and dry pipe systems (Figure 3).

Each provincial building code states that sprinkler systems must comply with the applicable National Fire Protection Association (“NFPA”) standard.
Critically, the 2026 edition of NFPA 25 clearly states that the property owner or their representative is responsible for “proper inspection, testing, maintenance, and impairment management of any water-based fire protection systems in accordance with this standard.”
As such, it is the responsibility of building owners and managers to ensure the requirements of NFPA 25 are met.
These standards are written to prevent sprinkler systems from freezing. When freezing does occur, it is often caused by either improper installation of the sprinkler pipes, insufficient insulation for the system, or improper ITM. All three situations signal a deviation from the NFPA standard.

A wet pipe sprinkler system is always pressurized with water. This means it can only be installed in temperature-controlled areas. Wet sprinkler systems should never be installed in areas where sub-freezing temperatures are possible. If the ambient temperature cannot be controlled, a wet pipe sprinkler system is not appropriate for the setting.
We often see freezing occur when wet sprinkler system pipes are unintentionally located in uninsulated spaces. Water-filled pipes can freeze even when only small lengths of pipe are exposed to unconditioned air due to defects in the insulation and/or building envelope or poor design (Figure 4 and Figure 5). One recurring issue we encounter is when an attic space is insulated along the false ceiling, below the sprinkler pipe, but not above it. In such cases, not only is the sprinkler pipe uninsulated from exterior air penetration, but the insulation below restricts conditioned air from the room from rising into the attic space (Figure 6).
The above scenarios represent installation and construction defects, which are the responsibility of the installation contractors and design/review consultants. NFPA 25 requires only visual inspections of sprinkler heads and pipes from floor level. This means the area behind drywall is not visually inspected. As such, it is unlikely that most of the above scenarios would be caught during NFPA 25 inspections.



Dry pipe sprinkler systems are used in areas that are not temperature-controlled, such as in attics above insulation, in garages, or on balconies. In a dry pipe sprinkler system, the pipes are filled with pressurized air from a compressor. The supply side of the system is connected to a specialized valve called a dry valve, which is kept closed by the air pressure. In the event of a fire, the sprinkler head will burst, the air pressure will be released, the valve will open, and water will enter the pipes.
In reality, water can still be periodically introduced into the system in standby. The air pumped into the dry pipes by the compressor will still contain humidity, which can condense and pool inside the pipes. Additionally, water will be introduced during the annual opening of the dry valve, which is part of regular ITM. This water must be removed prior to the onset of sub-freezing temperatures.
To facilitate drainage, NFPA 13 mandates that dry sprinkler pipes must be sloped towards designed low points in specific locations (Figure 7), and those low points must be connected to either the main drain valve or an auxiliary drain (Figure 8). Specifically, branch lines must be sloped 4 mm/m, and mains must be sloped 2 mm/m. Additionally, there must be a sign on the dry valve indicating the location of each low point drain.

Dry pipe system freezing is commonly caused by the creation of low points that cannot be drained. This could be due to improper pipe sloping that creates non-designed low points. During service, water will collect at those low points and will not be able to be removed by opening low-point drains, making the system susceptible to freezing.
As previously mentioned, it is not part of regular ITM to inspect the piping layout, unless modifications have been made recently to the system. As such, freezing due to piping layout is commonly caused by improper installation of the system, including issues with pipe sloping, and/or a lack of low-point drains with proper signage.

As part of regular ITM, NFPA 25 mandates that each drain must be opened in advance of cold weather. This is the last line of defence against freezing in dry pipe systems. However, if this step is not completed, the system is susceptible to freezing (Figure 9). As such, dry pipe freezing can be caused by improper ITM.
30 Forensic Engineering gets involved in many investigations of sprinkler system failures caused by freezing. We have extensive experience assessing failed sprinkler components and uncovering the root cause of the failure, allowing our clients to determine liability.
From a building owner’s or operator’s perspective, adherence to ITM requirements in NFPA 25 is key to ensuring these life-saving systems work as intended throughout the year. Adherence to these requirements works to prevent freezing failures, which can lead to significant water damage.